RI-17KA Operational Screens
On systems with the UV monitor, the system will display the same screens as on the Puretec
standard RI systems except the UV Intensity replaces the home screen. The UV Intensity
screen displays the level of UV light detected by the sensor. UV intensity can be affected by
poor water quality, scaling on the quartz sleeve and/or sensor, lamp failure or lamp expiring.
The following screens show the UV Intensity dropping.
Below 56%, the numbers and warning sign turn red and an audible chirp is given by the
ballast every 15 seconds. Below 51%, the screen is solid red and a constant audible alarm is
given. This alternates with a screen indicating “water may be unsafe for consumption”. With
the solenoid module, the controller de-activates the solenoid valve, shutting off all water flow.
RI-10K, RI-10KA, RI-17K & RI-17KA
Audible Chirp
Every 15 Seconds
Audible Chirp
Every 15 Seconds
Constant Audible
Alarm
Cycles With Red
Low UV Screen