To program the Advanced 5 for
Example 3 Reservoir Control (pump up)
by using the
Quick Setup
menu proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997
and press
ENTER
Using the ‘right arrow key go to
Quick Setup
menu press
ENTER
and as
prompted, by the questions, select the relevant option and
ENTER
.
Question
Option
Level, Pump Up/Down or
Differential
3 = Pump Up
No. of Pumps
2 = 2 Pumps
Pump Duty
3 = Alt DutAss
Pump No. 1
1 = Set to Relay 1
Pump No. 2
2 = Set to Relay 2
No. of Alarms
1 = 1 Alarm
Type Alarm 1
2 = Low
Alarm No.1
3 = Set to Relay 3
Xducer (P101)
2 = dB6
Measnt Units (P104)
1 = metres
Empty Level (P105)
3.5 (metres)
Span (P106)
2.8 (metres)
Programming is now complete and the unit can be returned to the run mode,
press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
,
and the Advanced 5 will return to the
Run Mode
.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed, and entering new values to relay setpoints as required.
Alternatively, the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...