U-Throated Flume
A
BSOLUTE
If the flow calculation is to be
absolute
P702
=
1
the flow will be calculated
using the formula: q = (2/3)
1.5
g
n
0.5
C
u
C
v
C
d
bh
1.5
Where: q = flowrate
g
n
= gravitational acceleration (nominal value = 980.66 cm/s
2
)
h = head
C
u
=
shape coefficient
calculated by the Flow 5
P724
C
v
=
velocity coefficient
calculated by the Flow 5
P721
C
d
=
discharge coefficient
calculated by the Flow 5
P722
b
=
throat width P711
R
ATIOMETRIC
U-Throated Flume
If the flow calculation is to be
ratiometric P702 = 2
the flow will be
calculated using the formula:
q= q
cal
(C
v
/C
vcal
)(C
d
/C
dcal
)(C
u
/C
ucal
)(h/h
cal
)
1.5
Where: q = flowrate
q
cal
=
flowrate at maximum head P705
Cv
=
velocity coefficient
calculated by the Flow 5
P721
Cv
cal
= velocity coefficient at maximum head
Cd
=
discharge coefficient
calculated by the Flow 5
P722
Cd
cal
=
discharge coefficient at maximum head
Cu
=
shape coefficient P724
Cu
cal
= shape coefficient at maximum head
h = head
h
cal
=
maximum head P704
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...