Page 104
Wait ….
Parameter
Default
Description
P101
Transducer
1 = dB Mach 3 Type of Transducer to be used.
P706
Volume Units
1 = Litres
Units of flow as on display and used
for calculations.
1=litres
3=cubic feet
5=US gallons
2 = cubic metres
4 = UK gallons
6 = Mil.USG
P707
Time Units
1 = per second
Units of time that volume units will
be displayed and calculated in.
1= units/sec.
3= units/hour
2= units/min.
4= units/day
P104
Measurement
Units
1 = metres
Units used to enter dimensions, and
displayed where appropriate.
1 = metres
3 = millimetres
5 = inches
2 = centimetres
4 = feet
P105
Empty Level
2.425 m
Distance from the end of the
transducer horn (dB Mach 3) or face
of the transducer to the material at
the bottom of the measuring element.
P703
Minimum
Head
0.000m
Distance from empty point (P105) to
zero flow.
P704
Max Head
2.425m
Distance from zero flow to max
flow. It should be noted that any
change to P704 updates P106 Span
and vice versa.
P824
Totaliser
Enable
1=On
Enables the flow totaliser, P820,
options are
0
=
Off
,
1
=
On
. Note this
totaliser can be viewed during run
via the totaliser “Hot Key” It can be
reset but only via P820, whilst in
“program mode”.
P816
Totaliser (R)
0=No
Enables the totaliser to be displayed
in the auxiliary display whilst in “run
mode”. Note this totaliser is
“resettable”, whilst in “run mode”,
via the totaliser hot key.
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...