Exponent Type
Formula
Exponent
K Factor
V-Notch Weir
Q=Kh
x
Where:
Q =Flow
K=
K factor
h=head
x
=
exponent
2.50
Automatically
selected by the
Ultra 5
Automatically
calculated,
dependent on
measurement,
flow and time
units chosen.
Other
Q=Kh
x
Enter value as
required
Enter value as
required
Contracted
Rectangular
Weir (With End
Contractions)
Q=K(L-0.2*h)h
x
Where:
Q =Flow
K=
K factor
L=crest length of weir
h=head
x
=
exponent
1.50
Automatically
selected by
Ultra 5
Automatically
calculated,
dependent on
measurement,
flow and time
units chosen.
R
ATIOMETRIC
If the flow calculation is to be
ratiometric P702 = 2
the flow will be
calculated using the formula: q = q
cal
(h/h
cal
)
X
Where: q = flowrate
q
cal
=
flowrate
at
maximum
head
(
705
)
h = head
h
cal
=
maximum head
(
P704
)
x
= exponent (determined as in absolute calculation above)
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...