Page
113
To program the Flow 5 for
Example 1 V-Notch Weir
by using the
Quick
Setup
menu proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997 and press
ENTER
Using the ‘right’ arrow key go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
Question
Option
PMD Type
1 = Exponent
Exponent
6 = V notch.
Calculation
2 = Ratiometric.
No. of Alarms
0 = No Alarms
Xducer
1 = dB Mach3
Volume Units
1 = Litres
Time Units
1 = Per Second
Measnt. Units
1 = metres
Empty Level
1.000 metres
Minimum Head
0.000 metres
Maximum Head
0.400 metres
Total Enable
1 = On
Totaliser (R)
0 = No
Total Multiplier
7 = 1000
Maximum Flow
96.5
Programming is now complete and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the Flow 5 will return to
Run Mode
.
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...