Page
131
R
ATIOMETRIC
V-Notch Angle Weir
(Non-BS 3680)
If the flow calculation is to be
ratiometric P702 = 2
the flow will be
calculated using the formula: q= q
cal
(h+kh/h
cal
+kh)
2.5
Where: q = flowrate
q
cal
=
flowrate at maximum head P705
h = head
kh = compensated head
Universal Calculations
Point of Measurement
The transducer must be above the
maximum head P704
by at least the near
blanking distance P107
.
For all
Universal
calculation applications, the point at which the head is
measured should be chosen such that the surface of the liquid is not effected
by turbulence.
Calculations
A
BSOLUTE
Universal Head Vs Flow
If the flow calculation is to be
absolute
P702
=
1
the flow will be calculated
using the formula: q = q(h)
Where: q
= flowrate
q(h) = flowrate for head
The desired number of
Breakpoints
,
(
P730 - P793
) are to be entered in
pairs in values of
head
and corresponding
flow
. (Minimum of 2 pairs of
Breakpoints is required).
Summary of Contents for ULTRA 5
Page 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Page 16: ...Page 8 Fascia Mount ...
Page 17: ...Page 9 Rack and Panel ...
Page 18: ...Page 10 This page left blank intentionally ...
Page 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Page 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Page 35: ...Page 27 This page left blank intentionally ...
Page 151: ...Page 143 This page left blank intentionally ...
Page 240: ...Page 232 This page left blank intentionally ...