PT610, PT620, PT630
Instruction Manual
56
01UN
(Could not read inputs)
Comments:
Input states are transmitted as a single ASCII character which is the hex. value of the binary state of the
inputs. 1 is on and 0 is off. 4-bit. ‘1111’ (inputs on) are represented as char ‘F’. To check the state of an
input in your software use bitwise AND (&)
[INPUTS]
value
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
Input 1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Input 2
ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF
Input 3
ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF
Input 4
ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF
V
|
Read digital outputs
Command
:
[ADR][V]
Response
:
[ADR][V][STATUS][OUTPUTS] (OUTPUTS is 2 bytes)
Example :
Command
: 01V
Response
: 01VA03
(Output 2 and Output 1 are active)
01VA06
(Outputs 3,2 are active)
01VA1F
(All 5 outputs are active)
01VN
(Could not read outputs)
Comments:
Output states are transmitted as 2 ASCII characters which are the hex. value of the binary state of the
outputs. 1 is on and 0 is off. 4-bit. ‘1111’ (outputs on) are represented as char ‘F’. To check the state of
an output in your software use bitwise AND (&)
[OUTPUTS]
value
0F 0E 0D 0C 0B 0A 09 08 07 06 05 04 03 02 01 00
Output 1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Output 2
ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF
Output 3
ON ON ON ON OFFOFFOFFOFF ON ON ON ON OFFOFFOFFOFF
Output 4
ON ON ON ON ON ON ON ON OFFOFFOFFOFFOFFOFFOFFOFF
Output 5
OFF OFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFF
[OUTPUTS]
value
1F 1E 1D 1C 1B 1A 19 18 17 16 15 14 13 12 11 10
Output 1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Output 2
ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF
Output 3
ON ON ON ON OFFOFFOFFOFF ON ON ON ON OFFOFFOFFOFF
Output 4
ON ON ON ON ON ON ON ON OFFOFFOFFOFFOFFOFFOFFOFF
Output 5
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
W
|
Set/Reset digital outputs
Command
:
[ADR][W][OUTPUTS]
Response
:
[ADR][W][STATUS]
Example :
Command
: 01W4296
Response
: 01WA
(Outputs 15,10,8,5,3,2 are activated)
01WN
(Outputs could not be activated)
Comments
:
Output states are transmitted as 2 ASCII characters which are the hex. value of the binary state of the
outputs. 1 is on and 0 is off. 4-bit. ‘1111’ (outputs on) are represented as char ‘F’. To selectively set the
state of the outputs in your software read the current state ([ADR][V]) and use bitwise logic for the new
data to write.
[OUTPUTS]
value
0F 0E 0D 0C 0B 0A 09 08 07 06 05 04 03 02 01 00
Output 1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Output 2
ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF ON ON OFFOFF
Output 3
ON ON ON ON OFFOFFOFFOFF ON ON ON ON OFFOFFOFFOFF
Output 4
ON ON ON ON ON ON ON ON OFFOFFOFFOFFOFFOFFOFFOFF
Output 5
OFF OFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFF