ENGLISH
Protectoplus Lager- und Umwelttechnik GmbH
, Tel. +49 4331/4516-0, Fax +49 4331/4516-11
Internet:
www.protecto.de
, E-mail:
- 58 -
•
After fastening the doubler plates, insert the firestop plugs (one each on the
inside and outside (see Figure 3).
Fig. 3
•
Feed the cables through, then seal the openings with the silicone which is
supplied with the product.
•
F30 cable / pipe bulkheads: Two doubler plates plus the wall plate on which
the bulkhead is installed -> wall thickness 120 mm
•
F90 cable / pipe bulkheads: Three doubler plates plus the wall plate on
which the bulkhead is installed -> wall thickness 150 mm
•
Note that the required wall thickness also includes a layer of internal
insulation (approx. 40 mm)
•
2 doubler plates: Max. cable diameter which can be fed through = 22 mm
•
3 doubler plates: No max. cable diameter