RLX-FHE, RLX-FHES, RLX-FHS
♦
RadioLinx FH
Hardware Installation
Frequency-Hopping Industrial Radio
Page 42 of 151
ProSoft Technology, Inc.
November 25, 2008
From left to right along the bottom of the radio enclosure:
Input power connector (Cage-clamp style connector). The input voltage
range is 6 to 28 VDC. An earth-ground connection can be connected to any
power supply earth ground or the chassis ground of an enclosure or cabinet
in various industrial applications.
Access hole for switching between the RS232 and RS485 operating modes.
(The switch itself is visible in the illustration below, which shows the RLX-FHS
model with its exterior chassis removed.)
RS485 connector (Cage-clamp). This connector supports both the 2-wire and
4-wire modes of operation (internal switch 3 sets the 2-wire vs. 4-wire
operating mode).
The vertical array of LED indicators at the right edge of the main RLX-FHS
enclosure, from top to bottom:
PWR (power indicator): green LED, lit when radio modem has power.
LINK (link indicator): green LED, indicates that a Remote radio has linked to
the Master radio (only valid for a Remote radio).
TRANSMIT (transmit data indicator): yellow LED.
RECEIVE (receive data indicator): green LED.
RS-232 (RS232 mode indicator): yellow LED, lit when radio is operating in
232 mode.
RS-485 (RS485 mode indicator): yellow LED, lit when radio is operating in
485 mode.
From left to right across the top of the enclosure:
ANT A and ANT B (antenna connections, reverse polarity SMA):
RS232 (DB-9) connector: The pin-outs are illustrated under RS-232 Cable
Specifications (page 44)