Configuring the EtherNet/IP Driver
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 46 of 154
ProSoft Technology, Inc.
July 24, 2018
Class 3 Client/UClient [x] Commands PLC5 ASCII
Parameter
Value
Description
Enable
Enable
Disable
Conditional Write
Specifies if the command should be executed and under what conditions.
E
NABLE
- The Command is executed each scan of the command list
D
ISABLE
- The command is disabled and will not be executed
C
ONDITIONAL
W
RITE
- The Command executes only if the internal data associated
with the command changes
Internal Address 0 to 9999
Specifies the database address in the modules internal database to be associated
with the command. If the command is a read function, the data received in the
response message is placed at the specified location. If the command is a write
function data used in the command is sourced from specified location.
Poll Interval
0 to 65535
Specifies the minimum interval to execute continuous commands. The parameter is
entered in 1/10 of a second. If a value of 100 is entered for a command the
command executes no more frequently than every 10 seconds.
Reg Count
1 to 125
Specifies the number of data points to be read from or written to the target device.
Swap Code
None
Word swap
Word and Byte swap
Byte swap
Specifies if the data from the server is to be ordered differently than it was received.
This parameter is typically used when dealing with floating-point or other multi-
register values.
N
ONE
- No change is made (abcd)
W
ORD SWAP
- The words are swapped (cdab)
W
ORD AND
B
YTE SWAP
- The words and bytes are swapped (dcba)
B
YTE SWAP
- The bytes are swapped (badc)
IP Address
xxx.xxx.xxx.xxx
Specifies IP address of the target device to be addressed by this command
Slot
-1
Specifies the slot number for the device. Use a value of -1 when interfacing to a
PLC5 These devices do not have a slot parameter. When addressing a processor in
a ControlLogix or CompactLogix, the slot number corresponds to the slot in the rack
containing the controller being addressed.
Func Code
150
151
152
Specifies the function code to be used in the command.
150 - Word Range Write
151 - Word Range Read
152 - Read-Modify-Write
File String
Specifies the PLC-5 Address as a string. For example N10:300
Comment
Optional 32 character comment for the command.