Configuring the EtherNet/IP Driver
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 38 of 154
ProSoft Technology, Inc.
July 24, 2018
3.5
Downloading the RSLogix 5000 Project to the Processor
1
Save, and then download the project to the processor.
2
A yellow triangle in RSLogix 5000 means an error on connection. Check that
the
O
UTPUT
size and
I
NPUT
size for the Class 1 connection in the gateway
configuration matches and the
C
OMM
F
ORMAT
is
INT
. Try increasing the
R
EQUESTED
P
ACKET
I
NTERVAL
time of module if the error persists.
3
Check the PLX82-EIP-PNC's IP address. This is located in the bottom left of
the
Diagnostics
page.
4
If errors persist, download the configuration again to make sure that the
module configuration matches the configured RSLogix 5000 program.
5
For additional troubleshooting, use the ProSoft Configuration Builder. Click on
P
ROJECT
>
M
ODULE
>
D
IAGNOSTICS
.
Class 1 displays the connection RPI time of processor and the IP address of
the module. The open connection count starts at 1 and increments if the
connection to the processor is interrupted or there is a connection timeout.
State, open connection, and connection timeout are controlled by the code.
You can change the RPI and Ethernet IP in the ladder configuration in
RSLogix 5000 (right-click
CONNECTION
1 and choose
P
ROPERTIES
).