PLX82-EIP-PNC ♦ Communication Gateway
Configuring the PROFINET Controller
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 51 of 154
July 24, 2018
4
Configuring the PROFINET Controller
Note: ProSoft fdt Configuration Software incorrectly allows for up to 36 PROFINET devices to be
configured with an "Update rate" as low as 1ms. Since that configuration can product over 70,000
frames per second, the PROFINET controller and devices will experience errors. ProSoft
Technology is in the process of adding limitations to the configuration software, and until then, we
have produced a guideline document to aid in the proper configuration of the PROFINET controller.
This guideline is available from the ProSoft website, accessible from the PLX82-EIP-PNC product
page. The file is named "ProSoft-PROFINET-Net-Load-Calv4.xlsx.