Configuring the EtherNet/IP Driver
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 44 of 154
ProSoft Technology, Inc.
July 24, 2018
Class 3 Client/UClient [x] Commands SLC500 3 Address Fields
Parameter
Value
Description
Enable
Enable
Disable
Conditional Write
Specifies if the command should be executed and under what conditions.
Enable - The command is execute each scan of the command list.
Disable - The command is disabled and will not be executed.
Conditional Write - The command executes only if the internal data associated
with the command changes.
Internal Address 0 to 9999
Specifies the database address in the module's internal database to be associated
with the command. If the command is a read function, the data received in the
response message is placed at the specified location. If the command is a write
function, data used in the command is sourced from a specified data area.
Poll Interval
0 to 65535
Specifies the minimum interval to execute continuous commands. The parameter is
entered in 1/10 of a second. If a value of 100 is entered for a command the
command executes no more frequently that every 10 seconds.
Reg Count
1 to 125
Specifies the number of data points to be read from or written to the target device.
Swap Code
None
Word Swap
Word and Byte Swap
Byte Swap
Specifies if the data from the server is to be ordered differently than it was received.
This parameter is typically used when dealing with floating-point or other multi-
register values.
None - No change is made (abcd)
Word Swap - The words are swapped (cdab)
Word and Byte Swap - The words and bytes are swapped (dcba)
Byte Swap - The bytes are swapped (badc).
IP Address
xxx.xxx.xxx.xxx
Specifies the IP address of the target device to be addressed by this command.
Slot
-1
Use a value of -1 when interfacing to an SLC 5/05. These devices do not have a
slot parameter. When addressing a processor in a ControlLogix or CompactLogix
rack, the slot number corresponds to the slot in the rack containing the controller
being addressed.
Func Code
502
510
511
Specifies the function code to be used in the command.
502 - Protected Typed Read
510 - Protected Typed Write
511 - Protect Typed Write w/Mask
File Type
Binary
Counter
Timer
Control
Integer
Float
ASCII
String
Status
Specifies the file type to be associated with the command.
File Number
-1
Specifies the PLC-5 file number to be associated with the command. If a value of -1
is entered for the parameter, the field will not be used in the command, and the
default file will be used.
Element Number
Specifies the element in the file where the command will start.
Sub-Element
Specifies the sub-element to be used with the command. Refer to the AB
documentation for a list of valid sub-element codes.
Comment
This field can be used to give a 32-character comment to the command.