PLX82-EIP-PNC ♦ Communication Gateway
Configuring the EtherNet/IP Driver
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 39 of 154
July 24, 2018
3.6
EIP Class 3 Server Connection
Use the EIP Class 3 Server connection in ProSoft Configuration Builder when the
gateway is acting as a server (slave) device responding to message instructions
initiated from a client (Controller) device such as an HMI, DCS, PLC, or PAC.
1
Within ProSoft Configuration Builder, click the [
+
] next to the gateway, then
click the [
+
] next to EIP Class 3 Server.
2
Double-click the second
EIP
C
LASS
3
S
ERVER
to display the
Edit - EIP Class
3 Server
dialog box.
3
Select the
Server File Size
(100 or 1000).
o
For a value of 100, the registers are from N10:0 to N10:99.
o
For a value of 1000, the valid registers are from N10:0 to N10:999.
Summary of Contents for PLX82-EIP-PNC