Setup
Page 38 of 87
NOTE: When mapping PLC5 Boolean files (e.g. B3), it is recommended that the
destination Logix tag be a SINT array, rather than a Boolean array. Using the
latter may result in unexpected results due to the packing format of Logix
Boolean arrays.
NOTE: When mapping PLC2 messaging, only INT datatypes will be supported.
Thus the Target Tag must be an array of INTs.
Figure 3.33 – Tag Browser tag selection
The two figures below show how DF1 messages are routed to the Logix tags using the DF1
Slave Map mode.
NOTE: It is your responsibility to ensure that the Logix tag array datatype and
size matches that of the DF1 File Number. Failing to do this can result in
communication faults.