Setup
Page 28 of 87
The required controller can then be chosen by selecting it and clicking the Ok button, or by
double-clicking on the controller module.
A maximum number of 20 mapping entries can be added.
Parameter
Description
DF1 Node Address
This parameter is one of the destination addresses that the PLX51-DF1-ENI will
accept. When the DF1 message initiator sends a message to a specific DF1 node
address that has been configured in the module, it will be accepted and routed
to the paired Controller Path.
This is the destination node address of the message, and not the source address
of the DF1 device.
Controller Path
The Ethernet/CIP path to the end device (e.g. Logix controller). Refer to the
additional information section in this document for references to details routed
CIP path information. For example:
If the controller (slot 0) is in a chassis with an Ethernet bridge (IP address
192.168.1.20) connected to the local network you would follow the format;
Ethernet bridge IP address, chassis backplane port, module slot etc.
192.168.1.20,1,0
For PLC5 and SLC500/MicroLogix devices, the path should contain only the
device’s IP address.
Enable CIP over DF1
This feature enables the PLX51-DF1-ENI to support CIP serial, allowing you to
program ControlLogix/CompactLogix controllers via the Serial Port.
Note: You will not be able to communicate over PCCC Direct and CIP at the
same time. If CIP over DF1 is enabled, the software automatically disables the
PCCC Direct option.
Enable PCCC Direct
The PCCC Direct option allows the PLX51-DF1-ENI to support the PCCC protocol
on a separate IP address. The PCCC protocol will allow the DF1 Router to
emulate a legacy controller (eg. SLC5/03) as if it is directly connected to the
Ethernet network.
PCCC Address
The PCCC Address allows the user to force the destination address of the DF1
message that is routed via the PCCC protocol or the CIP embedded PCCC
message. This is useful when using certain RSLinx Enterprise drivers in FTView
which does not allow the user to choose the destination DF1 Node address.
PCCC IP Address
The IP address of the supported PCCC Protocol.
Logix Connection
The connection class used by the mapped items to the Logix controller.
Table 3.3 - Bridge Map parameters