3.5.1.1.
BRIDGE MODE - REMOTE PROGRAMMING
The following example makes use of the PLX51-DF1-ENI to program multiple SLC / MicroLogix
stations connected on Ethernet, across a serial DF1 radio network.
Figure 3.19. – Remote Programming Example 1
The PLX51-DF1-ENI is configured in a Half-Duplex mode, to allow multiple EtherNet/IP
devices. The Bridge Mode configuration is configured to map the virtual node address 1 to
the SLC500 (192.168.1.241) and virtual node address 2 to (192.168.1.30).
Figure 3.20. – Remote Programming Example 1 – Bridge Configuration
RSLinx is configured using the DF1 Polling Master Driver. The DF1 settings should match those