Word Offset
Start End Name
Description
8 Module alarm CON
receive counter
Number of confirmation messages received from
slaves indicating that the slave received the
confirmation message from the MVI69-PDPMV1
module
9 Module acyclic
Read request
message counter
Number of acyclic read request messages sent by
the module
10 Module acyclic
Write request
message counter
Number of acyclic write request messages sent by
the module
11 Module backplane
read count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane read data transfers
12 Module backplane
write count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane write data transfers
13 Module backplane
error count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane data transfers that have
failed
14
File Error Word
This is bitmapped value that indicates which files are
not present.
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Problem with WATTCP.CFG file
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR
LED on the module will be illuminated.
15 27 Not
used
28 28 In mailbox queue
count
Number of message in the in mailbox queue
29 29 Out mailbox queue
count
Number of message in the out mailbox queue
30
30
Alarm queue count Number of message in the alarm queue
31 31 Last out mailbox
message ID
processed from
output image
Last out mailbox message ID processed from output
image
32 32 Current in mailbox
control index
Current in mailbox control index
33 33 Current alarm
control index
Current alarm control index
34
60
Reserved