6.2 PROFIBUS
DP
Architecture
The PROFIBUS DPV1 network supports multiple Master systems with several
slaves.
The most important features of PROFIBUS DPV1 are:
Standard
EIN 501 70
DIN 19245
Transmission Equipment
(Physical)
EIA RS-485
IEC 1158-2 (through link or coupler)
Fiber Optic Cable (not available)
Transfer Procedure
Half-duplex
Bus Topology
Linear bus with active bus termination
Bus Cable Type
Shielded twisted pair conductors
Connector 9-pin
D-Sub
Number of nodes on the bus
Max: 32 with no repeaters
Max: 125 with 3 repeaters in 4 segments
Effective Range
Max Bus Cable Length Per
Segment
Baud Rates (for 12 Mbit/sec cable)
1.2 km
9.6 kbps
1.2 km
19.2 kbps
1.2 km
93.75 kbps
1.0 km
187.5 kbps
0.5 km
500 kbps
0.2 km
1.5 Mbps
0.1 km
3 Mbps
0.1 km
8 Mbps
0.1 km
12 Mbps