MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
Mailbox Messaging
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 105 of 225
July 8, 2011
Response:
Message information (in response header)
"Invalid Data Size" is returned if Data size in the command header does not
equal 126.
If "Invalid Other" is returned, further information is to be found in Extended
word 8.
Additional Fault information (Extended word 7)
If Extended word 8 equals 0x000A -"Failed to execute request" additional info
can be found here.
Fault information (Extended word 8)
0x0001: Invalid setting in Message data word 1-63 of the command.
0x0002: At least one slave reports a warning. Refer to Message data word 1-
63.
0x000A: Failed to execute request. Additional fault information is to be found
in Extended word 7.
0x00FF: Module not initialized (this command is only possible after
END_INIT).
Message data word 1-63
Byte-array stating the status of the slaves. Array index is equal to slave
address.
0: Slave unaffected
1: Slave stopped
2: Warning - Slave could not be stopped because it is not part of the
configuration
3: Warning - Slave already stopped