MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 137 of 225
July 8, 2011
5.1.3 Viewing the Fieldbus Data from the MVI69-PDPMV1’s
Configuration/Debug Menu
Note: For this procedure, you must connect a serial cable from the serial port on your PC to the
RJ45 to DB9M adaptor cable on the MVI69-PDPMV1 module. If your 1769 processor is equipped
with a built-in Ethernet port, such as the L32E or L35E processors, you may make a diagnostic
connection to the module using CIPconnect.
1
In ProSoft Configuration Builder, select the
MVI69-PDPMV1
module, then
click the right mouse button to open a shortcut menu.
2
On the shortcut menu, choose
D
IAGNOSTICS
. This action opens the
Diagnostics
dialog box.
3
Press
[?]
to display the
Main
menu, and then press
[2]
to view Fieldbus data.
4
Note the value in Operation State. If the Master and the slave are
communicating correctly, the operation state will be C0 (hex).