Mailbox Messaging
MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 128 of 225
ProSoft Technology, Inc.
July 8, 2011
4.5
Mailbox Messaging Error Codes
4.5.1 Acyclic Message Status Word
This register contains bit and code information about the mailbox message. The
register is divided into five areas according to the following illustration:
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b
5
b4 b
3
b2 b1 b0
Message Type
ER
R
C/
R
(reserved) Error
Code
Bit / Field
Description
Contents
ERR
This bit indicates if the
received command contained
any errors.
0:
1:
Message OK
Error (See also "Error Code" below)
C/R
This bit specifies whether the
message is a command or a
response.
0:
1:
Response Message
Command Message
Error Code If the ERR bit is set, this field
contains additional information
about the error.
0h:
1h:
2h:
3h:
4h:
5h:
6h:
8h:
9h:
Fh:
Invalid Message ID
Invalid Message Type
Invalid Command
Invalid Data Size
Message header malformed (offset 008h)
Message header malformed (offset 00Ah)
Message header malformed (offset 00Ch to 00Dh)
Invalid Response
Flash Config Error
Invalid Other
(All other values are reserved)
Message
Type
This field specifies the type of
the message.
1h: Application Message
2h: PROFIBUS Specific Message
3h: Memory Message
5h: Reset Message
(All other values are reserved)