COOLER FAN PARAMETERS
Type
Min
Max
Unit
Def
F0
=0
fans
are
not
controlled
by
the
cooler
temperature.
=1
thermostat
function.
The
difference
between
the
ambient
and
the
cooler
temperature
is
used
to
control
the
fans.
=2
thermostat
function.
Only
the
cooler
temperature
is
used
to
control
the
fans.
C
0
2
Flag
1
F1
Fans
start-up
set
point:
F0=1
fans
ON
if
T
cooler
<
(Tambient-F1-A0)
fans
OFF
if
T
cooler
>
(Tambient-F1)
F0=2
fans
ON
if
T
cooler
<
(F1-A0)
fans
OFF
if
T
cooler
>
F1
S
-50
199
°C
/°F
*
F2
Fans
stops
when
cooling
(
0=no,
1=yes
).
Enable
if
F0=0
C
0
1
Flag
1
F3
Fans
stops
during
a
defrost
cycle
(
0=no,
1=yes
)
Independent
of
F0
C
0
1
Flag
*
Fd
Delay
after
draining.
Independent
of
F0
F
0
15
Min
0
H
OTHER
PARAMETERS
Type
Min
Max
Unit
Def
H0
Serial
address
C
0
15
-
1
H1
AUX
digital
output
configuration:
0=auxiliary
output
1
=alarm with contact normally opened (NO)
2=alarm
with
contact
normally
closed
(NC)
C
0
1
Flag
0
H2
0=keypad
disable
;1=
keypad
enable
;2=
keypad
&IR
disable
;
3=
IR
disable.
(note
IR=Infra
Red)
C
0
3
Flag
1
H3
Authorisation code for programming with the remote control
C
00
199
-
00
H4
0=
buzzer
enable
1=
buzzer
disable
C
0
1
Flag
0
IMPORTANT: to enable all the delays selected, you have to stop and restart the regulator.
Initial values
The following values are given as a guide and must be adapted in each case.
Positive
cold room
natural
defrost
Positive
cold room
electrical
defrost
Negative
cold room
Electrical
defrost
Password
22
22
22
/C
PROBE PARAMETERS
0
0
0
/2
Ambient
probe
gauging
4
4
4
/3
Measure
stability
8
8
8
/4
Probe
reading
speed
0
0
0
/5
Temperature
probes
mean
0
0
0
/6
Units °C / °F (0=°C, 1=°F)
0
0
0
Rd
Regulation
differential
(hysteresis)
2
2
2
r1
Minimal
set
point
authorized
to
the
user
0
-5
-30
r2
Maximal
set
point
authorized
to
the
user
20
20
-15
r3
Alarm
validation:
‘Maximal
time
reached
for
defrost
cycle‘
(
0=yes,
1=no
)
0
0
0
r4
Automatic
set
point
variation
with
switch
close.
(A4
or
A7
=7
)
3
3
3
r5
Mini/maxi
temperature
control
validation,
(0=yes,
1=no)
0
0
0
rt
Effective
interval
of
temperature
log.
-
-
-
rH
Maximal
temperature
logged
in
the
rt
interval
-
-
-
rL
Minimal
temperature
logged
in
the
rt
interval
-
-
-