38/61
Second
level:
configuration
parameters.
“C”
type.
The
password
is
needed
to
access
these
values.
To
change
the
value
of
one
of
these
parameters,
see
the
description
below:
Press
both
and
keys
simultaneously
for
at
least
10
seconds.
(In
the
event
of
a
fault,
stop
the
buzzer
first).
The
display
shows
“00”.
Press
the
or
key
to
display
“22”
which
is
the
default
password.
(This
password
can
be
changed)
Press
the
key
to
confirm
this
value
(password).
On
the
display,
the
first
parameter
code
is
displayed.
Press
the
or
key
to
change
the
parameter
code.
When
the
parameter
code
to
change
is
reached,
press
the
key
to
display
the
value
of
the
parameter
selected.
Change
the
parameter
value
using
the
or
keys.
When
the
parameter
value
is
reached,
press
the
key
to
temporarily
set
this
value
and
return
to
the
code
selection.
To
memorise
the
modified
values
and
return
to
the
main
page,
press
the
key.
To
end
the
configuration
without
memorising
the
modified
values,
wait,
without
touching
the
keypad,
for
at
least
60
seconds.
After
this
time
the
main
page
will
be
displayed
automatically.
PARAMETERS TABLE
Parameter
Type
Min
Max
Unit
Def
PASSWORD
C
00
+199
-
22
/
PROBE PARAMETERS
/C
Ambient
probe
gauging
S
-20
+20
°C
/°F
0.0
/2
Measure
stability
C
1
15
-
4
/3
Probe
reading
speed
C
1
15
-
8
/4
Temperature
probes
mean
C
0
100
-
0
/5
Units °C / °F (0=°C, 1=°F)
C
0
1
Flag
0
/6
Decimal
point
validation
(0=yes,
1=no)
C
0
1
Flag
0
r
REGULATION PARAMETERS
Type
Min
Max
Unit
Def
rd
Regulation
differential
(hysteresis)
S
0.1
+19.9
°C
/°F
2
r1
Minimal
set
point
authorized
to
the
user
C
-50
r2
°C
/°F
*
r2
Maximal
set
point
authorized
to
the
user
C
r1
+199
°C
/°F
*
r3
Alarm
validation:
‘Maximal
time
reached
for
defrost
cycle‘
(
0=yes,
1=no
)
C
0
1
Flag
0
r4
Automatic
set
point
variation
with
switch
close.
(A4
or
A7
=7
)
C
0
+20
°C
/°F
3.0
r5
Mini/maxi
temperature
control
validation,
(0=yes,
1=no)
C
0
1
Flag
0
rt
Effective
interval
of
temperature
log.
S
0
199
Hours
-
rH
Maximal
temperature
logged
in
the
rt
interval
S
-
-
°C
/°F
-
rL
Minimal
temperature
logged
in
the
rt
interval
S
-
-
°C
/°F
-