BL ALARM
Enables/disables the Backlight burnout detect function.
(Default : ON)
When a burned-out backlight is detected, the status LED
flashes alternately green and red, or a steady orange.
Touch-operation will be disabled when the backlight burns out,
which prevents the FP from sending input signals to the PLC.
SET
Applies the setting and returns to the main menu.
The H-POS might exceed its adjustable range when
analog RGB interface is applied. In that case, this function can
be effective for adjusting the out-of-range H-POS so that you
change the Polarity Lock from OFF to ON.
(Default: OFF <Polarity Lock function disabled>)
ESC
Cancels the setting and returns to the main menu.
SAVE
Saves all the adjusted settings in the EEPROM.
POLARITY LOCK
•
In the OSD, pressing the
SET
button applies the set value and enables the
setting. The set value won't be canceled unless the power is turned OFF or
the value is reset.
If the power is turned OFF without saving the set value, that data will
disappear. The last saved data will be read into the system when the FP
starts. To enable the changed value, be sure to press the
SAVE
button.
•
When the OSD automatically closes after 30 seconds of inactivity, the set
value that you were modifying at the time will be retained. If you quit the
OSD with the
ESC
button, the value that you were modifying will be not be
retained and the previously set value will be used.
• In the system setting screen, touching the value displayed on the panel changes
the value of the time period.
• Normally, the FP unit detects a backlight burnout by
monitoring the backlight's current flow, however, the
FP may fail to detect this condition, depending on the
type of backlight problem.
• The setting functions after the OSD closes.