under 4-R3
• Tightening the screws with too much force can damage the FP unit's case.
• The necessary torque is 0.5N•m.
• Depending on the installation panel's thickness, etc., the number of installation
fasteners used may need to be increased provide the desired level of moisture
resistance.
• Installation fastener model number : GP070-AT01.
Attach the Installation Fasteners from Inside the Panel
The following figures show the four (4) fastener insertion slot locations. Insert each fastener's
hook into the slot. Tighten the screws in a diagonal pattern, and slowly increase the torque.
Create a Panel Cut and insert the FP into the panel from the front
6
Wiring
Installation
fastener
FP
Panel
Unit: mm [in]
Panel
301.5
[11.87 ]
+1
0
+0.04
0
227.5
[8.96 ]
+1 0
FP
+0.04 0
Panel thickness
1.6mm[0.06in] to
10.0mm[0.39in]
•
To avoid an electric shock, when connecting the FP unit's power cord terminals to
the power terminal block, confirm that the power supply is completely turned OFF,
via a breaker, or similar unit.
•
FP2650-T41 unit is designed to use only AC100 to AC240V input. Any other power
level can damage both the FP and the power supply.
•
Since there is no power switch on the FP unit, be sure to attach a breaker-type
switch to its power cord.
• When grounding the FP's FG terminal, comply with the instructions. If the FP's FG
terminal is grounded appropriately, there is the danger of an electrical shock (pro-
tective earth) or the danger of FP malfunction (functional earth).
WARNINGS
Panel
FP
Top
Bottom
Insertion Slots