AFV-P Series High Performance Programmable AC Power Supply
11
2.3
Input Connection
The input terminals are located on the rear panel of the product (see Figure 2.2). The
input power cord must be rated at least for 85
C. The input power cord must have
rated current which is greater than or equal to the maximum input rated current of
the product.
See Figure 2.2 and do the following procedures step by step:
1. Remove the safety cover from the rare panel of the product.
2. Screw the power cord to the input terminals of the product as follows,
2.1 g
reen or yellow wire to the terminal “G”
of the input terminals;
2.2 w
hite or blue wire to the terminal “N”
of the input terminals; and
2.3 b
lack or brown wire to the terminal “L” of the
input terminals.
3. Slip the safety cover over the input terminals, and secure the cover with two
screws.
WARNING
Protective Grounding.
To protect users, the wire connected to terminal “G” (that
is GND) must be connected to the earth ground. Under no circumstances shall
this product operated without an adequate protective grounding connection.
Installation of the power cord to the product must be done by a professional and in
accordance with local electrical codes.
Figure 2.2 Input terminals