AFV-P Series High Performance Programmable AC Power Supply
67
Protection
2. High environmental tem-
perature.
for product ventilation
2. Use the vacuum cleaner
to clean the air inlet
3. Install the product on the
place with environmental
temperature not exceeding
40
C.
RCP
Reverse Current
Protection
Problems of the current
feedbacking from the load
to the inverter circuitries.
Remove the load to inspect
the output voltage.
Fan Fail
Fan Failure
Fault of the fan.
Seek the technical assis-
tance.
AMP Fail
Inverter Failure
1. Load oscillation
2. Problems of the voltage
feedbacking to the inverter
circuitries
3. Fault of the inverter cir-
cuitries.
1. Remove the load to in-
spect the output voltage.
2. Seek the technical assis-
tance.
Table 3.1 Troubleshooting Table