Model PD6262 Analog Dual-Input Rate/Totalizer Instruction Manual
87
Meter Copy or Cloning Instructions
!
Caution!
Do not connect the two meters to
the same signal source while
cloning. Internal calibration may
be affected.
1. Connect two meters using a PDA1200 meter copy cable.
2. Do not connect the two meters to the same signal source.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter
the
Advanced
Features
menu of the Master meter; see
Advanced Features Menu
on page 70.
5. Scroll to the
Copy
function using the Up
arrow button then press
Enter.
6. The meter displays the message
Send
. Press Enter, the display
flashes while sending data. The message
done
is displayed when
copying is completed.
7. The Clone meter displays the message
CPY Rc
while being
programmed then the message
done
when copying is completed.
The meter initializes and returns to Run Mode using the same
settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer
to
Copy Function Requirements
above.
Copy Function Requirements
To successfully copy settings from one meter to another, both meters
must have the same software version and the same baud rate setting.
See
Determining Software Version
,
page 90 for instructions.