™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
48
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
20 nmA
20 mA output
Enter mA output value read
by milliamp meter with at
least 0.001 mA resolution
user
User I/O
Assign function keys and
digital I/O
F1
F1 function
key
Assign F1 function key
F2
F2 function
key
Assign F2 function key
F3
F3 function
key
Assign F3 function key
F4
F4 function
Assign F4 function
(digital input)
dI I
Digital input
1
Assign digital input 1
– 8,
if expansion modules are
connected
dO 1
Digital output
1
Assign digital output 1
– 8,
if expansion modules are
connected
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
Info
Information
Display software (firmware)
information
erase
Erase
Erase MeterView Pro
software stored in
controller’s memory
Function Keys Operation
During operation, the programmable function keys
operate according to the way they have been
programmed in the
Advanced Features
– User
menu.
Programmable Function Keys User Menu
for details. The following table shows the
default setting for each of the function keys.
Function
Key/Button
Default
Setting
Action
F1/START
Start
Start batch
F2/BATCH
preset
Change preset
F3/STOP
stop
Pause/stop
batch
F4/Digital Input
Srtstp
Start/stop batch
F4 Operation
A digital input, F4, is standard on the controller. This
digital input is programmed identically to function keys
F1, F2, and F3. The input is triggered with a contact
closure to COM, or with an active low signal. During
operation, F4 operates according to the way is has
been programmed in the
Advanced Features
– User
menu. See
Programmable Function Keys User Menu
•
Only STOP Operation Enabled if a Batch is
Running.
During a batch process, the only
function that can be performed is the pause/stop
functions of the STOP button; the default
programming of the F3 key. No other functions,
including min/max display, manual alarm reset, or
total reset, will function while a batch is running.