P
RO
V
U
™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
40
Scaling the 4-20 mA Analog
Output (
Aout
)
The 4-20 mA analog output can be scaled to provide
a 4-20 mA signal for any rate display range selected.
No equipment is needed to scale the analog output;
simply program the display values to the
corresponding mA output signal.
The
Analog Output
menu is used to program the
4-20 mA output based on rate display values.
For instructions on how to program numeric values,
see
Reset Menu (
reset
)
The
Reset
menu is used to reset the total, grand
totals, batch count, maximum, or minimum reading
(peak or valley) reached by the process; both
maximum and minimum may be reset at the same
time by selecting “reset high & low” (
rst HL
).
Manual Control Menu (
Contrl
)
The Manual Control menu is used to control the
4-20 mA analog output and the relays manually,
ignoring the input. Each relay and analog output can
be programmed independently for manual control.
Selecting automatic control sets all relays and analog
output for automatic operation.