™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
47
Advanced Setup &
Programming
In addition to the functions described in
operation and display features may be programmed.
Please note that configuring these features may
disable some default batch controller features or it
can make running a batch operation impossible.
These functions should only be used by users who
are sure of their need in their application.
Advanced Features Menu
To simplify the setup process, functions not needed
for most applications are located in the
Advanced
Features
menu.
Press and hold the Menu button for three seconds to
access the advanced features of the controller. This
cannot be done during a batch process as all
functions other than STOP are disabled during a
batch process, including the Menu button.
Advanced Features Menu &
Display Messages
The following table shows the functions and
messages of the
Advanced Features
menu in the
order they appear in the menu.
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
Gate
Gate
Gate settings
Lo G
Low Gate
Program low gate value
Hi G
High Gate
Program high gate value
filter
Filter
Set noise filter value
Hi Spd
High Speed
Filter
Program High Speed Filter
Lo spd
Low Speed
Filter
Program Low Speed Filter
Round
Round
Set the rounding value for
display variables
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
seriAl
Serial
Set serial communication
parameters
SlaVId
Slave ID
Set slave ID or controller
address
baud
Baud rate
Select baud rate
Tr dLY
Transmit
delay
Set transmit delay for serial
communication
Parity
Parity
Select parity
Even, Odd, or None with 1
or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu
(function, cutoff, out)
Functn
Input Signal
Conditioning
Select linear
Linear
Linear
Set controller for linear
function and select number
of linearization points
No PtS
Number of
points
Set controller for 2 to 32-
point linearization
CutofF
Cutoff
Set low-flow cutoff
Count
Count
Set the totals to count up or
down from a set value
Tot C
Total count
Set the batch to count up to
or down from the preset
up
Up
Set the total to count up
Douwn
Down
Set the total to count down
Gtot C
Grand total
count
Set the grand total to count
up or down from a defined
value
C strt
Count start
Set the starting grand total
value when counting down
AoutPr
Analog
output
programming
Program analog output
parameters
Source
Source
Select source for the 4-20
mA output
O-rang
Overrange
Program mA output for
display overrange
u-rang
Underrange
Program mA output for
display underrange
Force
Force output
Force analog output value
for loop break
Ignore
Ignore
Ignore loop break condition
nmAx
Maximum
Program maximum mA
output allowed
nmin
Minimum
Program minimum mA
output allowed
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 nmA
4 mA output
Enter mA output value read
by milliamp meter with at
least 0.001 mA resolution