™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
12
Isolated 4-20 mA Transmitter
Output
Output
Source
Rate/process, total, grand total, max, min,
set points 1-8, Modbus register, or manual
control mode
Scaling Range
1.000 to 23.000 mA for any display range.
Calibration
Factory calibrated:
4.000 to 20.000 = 4-20 mA output
Analog Out
Programming
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and
break
Accuracy
± 0.1% FS ± 0.004 mA
Temperature
Drift
0.4 µA/
C max from 0 to 65
C ambient,
0.8 µA/
C max from -40 to 0
C ambient
Note: Analog output drift is separate from
input drift.
Isolated
Transmitter
Power Supply
Terminals I+ & R: 24 VDC
10%. May be
used to power the 4-20 mA output or other
devices.
All models rated @ 40 mA max.
External Loop
Power Supply
35 VDC maximum
Output Loop
Resistance
Power supply Minimum Maximum
24 VDC
10
700
35 VDC
(external)
100
1200
Additional
4-20 mA
Outputs
The
can split the optional
4-20 mA output into two isolated 4-20 mA
outputs
0-10 VDC
Output
The
can convert the
optional 4-20 mA output to a 0-10 VDC
output
USB Connection
Function
Programming only
Compatibility
USB 2.0 Standard, Compliant
Connector Type
Micro-B receptacle
Cable
USB A Male to Micro-B Cable
Driver
Microsoft
®
Windows
®
XP/Vista/7/8/10
Power
USB port provides power to the
controller for configuration only.
DO NOT apply AC or DC power to the
controller while the USB port is in use.
On-Board Digital Input (F4)
Function
Start/Stop batch, remote operation of front-
panel buttons, acknowledge/reset relays,
reset max/min values. See
Digital I/O Available Settings
on page
a complete list of capabilities.
Contacts
3.3 VDC on contact. Connect normally
open contacts across F4 to COM
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Additional I/O
Up to 2 external modules, model
with 4 digital inputs and 4 digital outputs
each can be added.
Modbus
®
RTU Serial
Communications
Slave Id
1
– 247 (Controller address)
Baud Rate
300
– 19,200 bps
Transmit
Time Delay
Programmable between 0 and 199 ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte
Timeout
0.01
– 2.54 second
Turn Around
Delay
Less than 2 ms (fixed)
Note: Refer to the P
RO
V
U
Modbus Register Tables located
MeterView Pro
Availability
Download directly from controller or
from
www.predig.com/download_software
System
Requirements
Microsoft
®
Windows
®
XP/Vista/7/8/10
Communications
USB 2.0 (for programming only)
(Standard USB A to Micro USB B)
RS-232 adapter, RS-485 adapter and
RS-485 to USB converter
(programming, monitoring, batch
control, and data logging)
Configuration
Configure controllers one at a time
Power
USB port provides power to the
controller for configuration only.
DO NOT apply AC or DC power to the
controller while the USB port is in use.
Batch Control
Use MeterView Pro to control the
batch, change the preset, reset totals,
and test the relays.
Data Logging
Use MeterView Pro for data logging of
the batch process.