![Precision Digital Corporation ProVu PD6310-WM Instruction Manual Download Page 14](http://html.mh-extra.com/html/precision-digital-corporation/provu-pd6310-wm/provu-pd6310-wm_instruction-manual_1594189014.webp)
P
RO
V
U
™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
14
Panel Mounting Instructions
•
Prepare a standard 1/8 DIN panel cutout
–
3.622" x 1.772" (92 mm x 45 mm). Refer to
Figure 1. 1/8 DIN Panel Cutout
below for more details.
•
Clearance: allow at least 6.0" (152 mm) behind
the panel for wiring.
•
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
•
Remove the mounting bracket mounted on the
controller (back-off the screw so that there is ¼"
(6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Note what side this bracket is mounted to.
•
Locate the security bracket packed in the wire
security seal kit. The security bracket can be
identified by wire loop pass-through located next
to the mounting screw.
•
Insert controller into the panel cutout.
•
Mount each bracket. Be sure the security bracket
is located on the side of the case with the wire
loop pass-through holes.
•
Tighten the screws against the panel. To achieve
a proper seal, tighten the mounting bracket
screws evenly until controller is snug to the panel
along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
DO NOT apply AC or DC power to the controller when using the
Micro USB connection.
Figure 1. 1/8 DIN Panel Cutout and Mounting
Mounting Dimensions
Figure 2. Controller Dimensions - Side View
Figure 3. Controller Dimensions - Top View
NO
NC
NC
C
NO
C
NO
NC
NC
C
NO
C
+
-
R
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)