PHYSICAL FEATURES AND REQUIREMENTS
164201409---3
A---15
Powerware BPIV Parallel Cabinet Installation and Operation
164201409 REV. B
101503
1.
The Parallel Cabinet equipment operating environment must meet the size and weight
requirements shown in Table R, according to your Parallel system configuration.
2.
In the Parallel System, the UPMs, and Battery cabinets are palleted separately for
shipping.
3.
Do not tilt cabinets more than
10
˚
during handling.
4.
Dimensions are in millimeters (inches).
Table R Equipment Weight
Table R. Equipment Weight
Component
Configuration
Weight
Kg (lb)
Component
Configuration
Shipping
Installed
Point Loading
3+1
143 (315)
116 (255)
4 at 29 (63.8)
Parallel Cabinet
Powerware BPIV---15 kVA
2+1
134 (295)
107 (235)
4 at 26.8 (58.8)
Powerware BPIV---15 kVA
1+1
125 (275)
98 (215)
4 at 24.5 (53.8)
3+1
159 (350)
132 (290)
4 at 33 (72.5)
Parallel Cabinet
Powerware BPIV---30 kVA
2+1
145 (320)
118 (260)
4 at 29.5 (65)
Powerware BPIV---30 kVA
1+1
132 (290)
104 (230)
4 at 26 (57.5)
5.
The clearances required around the Parallel Cabinet are shown in Table S.
Table S. System Clearances
From Front of Cabinet
36 inches working space
From Back of Cabinet
6 inches air circulation clearance
From Sides of Cabinet
Allow installation working space
6.
The basic environmental requirements for operation of the Parallel Cabinet are:
Ambient Temperature Range:
0---40
˚
C (32---104
˚
F)
Recommended Operating Range:
20---25
˚
C (68---77
˚
F)
Maximum Relative Humidity:
95%, non-condensing