Product Specifications
7.1
Model Numbers
The Parallel cabinet is freestanding, with safety shields behind the front panel. The
Parallel cabinet is available in two output power ratings and three configurations.
System
UPS Models
Configuration
Powerware BPIV
15
kVA
1 Capacity/1 Redundant
Powerware BPIV
15
kVA
2 Capacity/0 Redundant
Powerware BPIV
15
kVA
2 Capacity/1 Redundant
Powerware BPIV
15
kVA
3 Capacity/0 Redundant
Powerware BPIV
15
kVA
3 Capacity/1 Redundant
Powerware BPIV
30
kVA
1 Capacity/1 Redundant
Powerware BPIV
30
kVA
2 Capacity/0 Redundant
Powerware BPIV
30
kVA
2 Capacity/1 Redundant
Powerware BPIV
30
kVA
3 Capacity/0 Redundant
Powerware BPIV
30
kVA
3 Capacity/1 Redundant
The following sections detail the input, output, and environmental specifications for the
Parallel cabinet.
7.2
Parallel Cabinet Input
Operating Input
Voltage
(UPM Dependent)
208 VAC nominal (50/60 Hz)
Operating Input
Frequency Range
3 Hz of nominal (50 Hz or 60 Hz)
Operating Bypass
Current
Model 15 kVA (1 Capacity/1 Redundant):
41.4 Amps
Model 15 kVA (2 Capacity/0 Redundant):
83.2 Amps
Model 15 kVA (2 Capacity/1 Redundant):
83.2 Amps
Model 15 kVA (3 Capacity/0 Redundant):
124.8 Amps
Model 15 kVA (3 Capacity/1 Redundant):
124.8 Amps
Model 30 kVA (1 Capacity/1 Redundant):
83.3 Amps
Model 30 kVA (2 Capacity/0 Redundant):
166.6 Amps
Model 30 kVA (2 Capacity/1 Redundant):
166.6 Amps
Model 30 kVA (3 Capacity/0 Redundant):
249.9 Amps
Model 30 kVA (3 Capacity/1 Redundant):
249.9 Amps