background image

EN 

 

EN

EN 

3.  OPERATION 

 
3.1 Starting Up 

After the UPS is connected to a power outlet, the UPS enters Standby mode. 

To turn on the UPS, press down the 

  button. After the UPS is turned on, it 

enters  Normal  mode.  The 

  indicator

 

will

  light

  indicating  that  power  is 

available from the UPS output receptacles. 

3.2 Starting the UPS on Battery mode 

NOTE

 

The  UPS  will  not  detect  the  input  frequency  automatically  when 

starting on battery; the default frequency is set to 

50Hz.

 

To  turn  on  the  UPS  without  utility  power,  press  down  the 

  button.  The 

UPS  will  also  supply  power  to  the  connected  equipments  and  operate  in 
Battery Mode. At the meantime, the 

  indicator

 

will

 flash

 and the alarm 

will sound every 10 seconds. 

3.3 Muting the Buzzer 

Press down the 

  button to initiate the Muting function in Battery mode. If 

you want to release the muting, press up the 

  button.   

NOTE

 

The  Muting  function  only  can  be  initiated  in  Battery  mode,  and  the 

alarm will continue beeping if there is a UPS fault, low battery condition, or if 
the battery needs to be replaced.   

3.4 Turning the UPS off 

To turn off the UPS, press and release the 

  button and  then unplug the 

UPS  from  the  power  outlet.  If  you  do  not  unplug  the  UPS,  it  remains  in 
Standby mode. 

3.5 Standby Mode 

When  the  UPS  is  turned  off  and  remains  plugged  into  a  power  outlet,  the 
UPS is in Standby mode. All indicators are off and power is not available to 
your equipment. The battery recharges when necessary. 

Summary of Contents for VI 1000RT/LE

Page 1: ...EN EN EN Pure Sine Wave Line Interactive UPS PowerWalker VI 1000RT LE PowerWalker VI 1500RT LE Manual EN Uninterruptible Power Supply System...

Page 2: ......

Page 3: ...This UPS is designed for Commercial Industrial use only It is not intended for use with life support application and other designated life critical devices 3 Do not remove the input power cord when th...

Page 4: ...uld be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA 12 Attention hazardous through electric shock Also with disconnection of this unit from the...

Page 5: ...it is available through serial or USB ports located on the rear panel The serial port will support communications directly with a server The communications protocol for the serial ports shall conform...

Page 6: ...tential power problems Figure 1 shows the UPS front panel indicators and controls Figure 1 Front Panel Description The UPS has a visible indication about the load level in line mode and the battery ca...

Page 7: ...ptional The 1st to 4th green Led lighting to indicate battery capacity LED1 green battery voltage 12 5V BAT LED2 green battery voltage 11 5V BAT LED3 green battery voltage 11 0V BAT LED4 green battery...

Page 8: ...1 3 UPS Rear Panels This section shows the detailed information about the UPS rear panels Figure 3 Rear Panel Description 1000VA 1500VA...

Page 9: ...representative 2 2 Installing the UPS The following steps explain how to install the UPS Figure 4 shows a typical installation only See UPS Rear Panels on page 8 for the rear panel of each model 1 If...

Page 10: ...wer Configuration Setup There are four pieces of plastic stand components accompanied with 1000VA 1500VA models Two pieces can be assembled to one complete stand In tower configuration use the two sta...

Page 11: ...stands carefully 2 Rack Mount Configuration Setup This UPS can be installed into standard 19 rack It requires the height of 2U from the rack Use the following procedure to install the UPS into a rack...

Page 12: ...screw holes on the side of the UPS and screw together Mind the Left and Right plates fixing as below 3 Fix the slide to the rack enclosure with screws 4 Insert UPS into the slide assemblies and lock...

Page 13: ...out of the stands Place the UPS on flat area with a soft and clean cushion 2 Align the mounting bearings with screw holes on the side of the UPS 3 Align the mounting ears with screw holes on the side...

Page 14: ...Tower Configuration 1 Unscrew the UPS from the Rack enclosure 2 Unscrew the ears and the bearings from the UPS 3 Slide down the UPS vertically and put the UPS stands at the end of the tower Place the...

Page 15: ...At the meantime the indicator will flash and the alarm will sound every 10 seconds 3 3 Muting the Buzzer Press down the button to initiate the Muting function in Battery mode If you want to release th...

Page 16: ...t normally open pull to Pin 5 when battery low alarm in battery mode 2 TxD Output TxD 3 RxD Input RxD 4 DTR Input tied to pin 6 5 Common Common tied to chassis 6 DSR Output tied to pin 4 7 RTS Input N...

Page 17: ...511C1 01220 0100 478DF2A After the software is successfully installed the communication with UPS has been established and a green icon will appear in the system tray Double click the icon to use the m...

Page 18: ...e equipment you are protecting to the jack labeled OUT and connect the network cable to the jack labeled IN 5 BATTERY REPLACEMENT 5 1 1000VA 1500VA models Follow the steps and charts below to replace...

Page 19: ...a 5 Disconnect the BLACK battery cable 6 Reconnect the BLACK battery cable to the new batteries 7 Slide the new batteries into battery case 8 Reconnect the battery cable and screw up the battery brack...

Page 20: ...2 7 ms typical 10ms max Efficiency Normal Mode 95 Rated full load battery full charged Boost Buck Mode 90 Rated full load battery full charged Battery Mode 80 Rated full load battery full charged Bat...

Page 21: ...Charger fail Red LED Blinking Audible alarm Back up mode Sounding every 10 seconds Battery low Sounding every 1 second Overload Sounding every 0 5 seconds Over charge Sounding every 1 5 seconds Over...

Page 22: ...may need to be charged or service Replace the battery Sounding every 5 0 seconds Charger fail Please contact your local dealer Continuously sounding The UPS fails or fan fault Please contact your loca...

Page 23: ...ed cable 2 Ensure the load does not exceed the maximum rating of UPS Back up time of the battery has been reduced Battery is not charged Re charge the battery at least 24 hours The UPS fault LED is bl...

Reviews: