EN
EN
–
EN
Fan Fault (Fault)
Red LED and LED1 (the first green) Lighting
Output
Voltage
low (Fault)
Red LED and LED2 (the 2
nd
green) Lighting
Output
Voltage
high (Fault)
Red LED and LED3 (the 3
rd
green) Lighting
Output
Short
Circuit (Fault)
Red LED and LED4 (the 4
th
green) Lighting
Overload (Fault)
Red LED Lighting and LED5 (green) blinking in Bat mode, lighting in Line
mode
- Battery replace
Red LED Blinking
- Over charge
Red LED Blinking
- Charger fail
Red LED Blinking
Audible
alarm
- Back up mode
Sounding every 10 seconds
- Battery low
Sounding every 1 second
- Overload
Sounding every 0.5 seconds
- Over charge
Sounding every 1.5 seconds
- Over temperature
Sounding every 2.5 seconds
- Battery replace
Sounding every 3 seconds
- Charger fail
Sounding every 5 seconds
- Fault
Continuous sounding
Dimensions
and Weights
Dimensions(L*W*
H mm)
390*86*328
Weight(kg)
8.62
10.36
Environment
and Safety
Operating
Temperature
0
℃
to +40
℃
Relative Humidity
0 to 90% Relative Humidity (Non-condensing)
Audible Noise @1
meter
<45 dBA
Safety
Conformance
EN62040-1-1, CE
EMC (Class A)
EN62040-2 C2
Summary of Contents for VI 1000RT/LE