R&D – PROCEDURA START-UP DT 0419 – E02
4.9
INSTRUCTIONS FOR SWITCHING SYSTEM IN POWER SAVE MODE TO MANUAL BYPASS MODE
If for maintenance purposes or other reasons the UPS must be excluded from the system, providing at the
same time mains power to the critical load, proceed as follows:
1. Turn off the inverter
Using menu
1. CONTROL MODE
select
Inverter ON/OFF
and press ENTER
This turns off the inverter and uninterrupted supply is no longer guaranteed to the load
2. Close MANUAL BY-PASS (I3) switch
Remove the padlock (or any other mechanical safety lock) from the switch and lift the knob to ON
position
3. Open the INPUT MAINS (I1) switch
4. Open the INPUT RESERVE (l2) switch
The load is supplied directly from the mains through the manual By-Pass
5. Open UPS OUTPUT (I4) switch
6. Disconnect the battery
At this point the load is supplied directly by the reserve network
and inside the UPS there are not hazardous voltages, except of the compartment
(covered with metal panel) where the input and output cables are connected,
and - for few minutes - inverter DC and AC capacitors (also covered with metal panel).