POWERTRONIX SpA reserves the right to modify this document without any notice
Pag. 25 di 41
R&D – PROCEDURA START-UP DT 0419 – E02
3.5
UPS IN FAULT CONDITIONS
If the UPS experiences the fault, the normal status message will be replaced with the alarm one.
An alarm message will differ depending on the type of fault which occurred. Activated sound signal can be
switched off by pressing the ESC key. The ENTER (< >) key can be used to display the list of indications
which let the operator to understand the meaning of the alarm. The <BACK or NEXT> keys can be used to
scroll through all the active alarms. When the alarm cause disappears, the LCD will return to the default
message.
The possible alarms and associated with them help messages are listed below.
ALARM MESSAGE
MEANING
INVERTER OFF
The load is no longer supplied by the inverter
and subject to any mains failures
INVERTER OVERLOAD
The inverter is off due to an overload and the load
is supplied by the reserve network
STATIC SWITCH LOCKED
After 3 unsuccessful automatic switching attempts from
the reserve to inverter, the UPS blocks the static switch
in the reserve network position
BATTERY TEST FAILURE
Displayed whenever the periodic test on the battery
fails for any reason
BATTERY PRE-ALARM
At the battery voltage of around 345V the UPS warns
the user of a low battery voltage
At 320V discharging ends and the UPS switches off
STATIC SWITCH FAILURE
At least one of output phases is missing
MANUAL BYPASS ON
The manual bypass switch has been closed
MAINS OUT OF LIMITS
The mains voltage is out of allowed specification,
it might be out of the range allowed by the system, or
simply not present
BY-PASS OUT OF LIMITS
The reserve is out of allowed specification, it might be
out of the range allowed by the system, or
with incorrect cyclic direction, or not present
EMERGENCY POWER OFF
Displayed whenever the E.P.O. button is pressed
PARALLEL DATA EXCHANGE
FAILURE
This alarm occurs when there is, for any reason, no
data exchange between UPS units in parallel.
It may be due to a missing or incorrect connection
of one or more parallel fibers
BATTERY CHARGER FAILURE
Battery charger doesn’t work properly or is not
connected
UPS ALARM
ALARM
CAUSE
<ENTER>
< BACK or NEXT
>