R&D – PROCEDURA START-UP DT 0419 – E02
2.8.1
REMOTE PANEL (OPTIONAL)
Remote panel is connected to the UPS via the terminal board M1 located on the remote communication
board (CS0118)(connection diagram fig. 2.8b). This device is used for remote monitoring of the main UPS
blocks, the status of the main blocks is represented through LED, and there is also an acoustic alarm,
which can be shut off with key 5.
LED description
1) Green ON UPS LED
If it’s on, the UPS is operating correctly
If it’s off, indicates that one or more inverter section alarms are present
(acoustic alarm enabled)
2)Yellow ON BATTERY LED
If it’s on, the UPS is operating on battery
(acoustic alarm enabled)
3) Red LOW BATTERY LED
If it’s on, indicates imminent end of battery discharge
(acoustic alarm enabled)
4) Yellow ON BYPASS LED
If it’s on, indicates load supplied from reserve
(acoustic alarm enabled)
5) ALARM SILENCE key
Used to switch off the acoustic alarm
6) Green LED
If it’s on, indicates correct power supply connected to the panel
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
11
12
DB9
Male Connector
5
9
4
8
3
7
2
6
1
RELAY 2P-2S
K1
9
NOTE:
2,5,8,11
1
Battery LOW
ON CS0118 COMMON TAGBLOCKS MUST
BE LINKED TOGETHER
4
5
On By-pass
CS0118
Relay
Board
2
Ups ON
UPS
REMOTE
PANEL
1
4
EXT SUPPLY
M1
12
3
Common
UPS Remote
Panel
Mains Status
CS0118 Relay Board
fig. 2.7.2b