50
Load Break Switch Control
ERT-200S
7.
Operation Setting
7.1.
Operation Setting
Select
“
Function
Setting” in the main menu, and move to this menu by pressing ENTER.
“Operation
Setting
” menu has the following submenu.
7.1.1.
Phase Fault Setting
Range
Step
Def.
Unit
Min
Max
Function Use
No
Yes
No
PickUp Current
5
900
1
400
A
Detection Time
0.05
10.00
0.01
0.05
Sec
Inrush Restraint
No
Yes
No
Cold Load Pick Up
100
500
10
200
%
Cold Load Time
0.1
180.0
0.1
0.2
sec