62
Load Break Switch Control
ERT-200S
UFR / Pick-up Frequency Set
Range
45.00 ~ 60.00 Hz
Default
49.80Hz
Step
0.01Hz
Set Pickup Frequency.
UFR / Pick-up Voltage Set
Range
50 ~85 %
Default
80%
Step
1 %
Set pickup voltage.
UFR / Delay Time Set
Range
0.1
20.0 sec
Default
1.0 s
Step
0.1 s
Set Delay Time
UFR / Function use
Range
Yes / No
Default
No
Step
Set
[Use / No Use]
of direction Detection, when occurs
Ground fault.
7.1.10.
Over Frequency Setting
Range
Step
Def.
Unit
Min
Max
F-Pick Up
50.00
70.00
0.01
62.20
Hz
V-PickUp
50
85
1
80
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No Use
Use
No Use