60
Load Break Switch Control
ERT-200S
Sectionalize / Fault count Set
Range
Default
Step
Set
[Use / No Use]
of direction Detection, when occurs
Sectionalizer.
7.1.8.
SEF Setting
Range
Step
Def.
Unit
Min
Max
I-Pick Up
2
20
1
5
A
V-PickUp
10
80
1
30
V
Angle
0
90
1
90
Deg
Detection Time
0.1
300.0
0.1
0.1
sec
Inrush Rest
No
Yes
No
Function Use
No
Yes
No
SEF / Pick-up Current Set
Range
2 ~ 20 A
Default
5 A
Step
1A
Set Pickup current.
SEF / Pick-up Voltage Set
Range
10 ~ 80V
Default
30V
Step
1 V
Set pickup voltage.
SEF / Angle Set
Range
0 ~ 90 deg
Default
0 deg
Step
1 deg