background image

1

DIMENSIONS  In inches (mm)

PANEL CUT-OUT

!

2 LINE X 40 CHARACTER LIQUID CRYSTAL DISPLAY WITH LED

BACKLIGHT

!

250 ALARM POINT LOGGER

!

RECIPE HANDLING

!

COMPREHENSIVE REPORT GENERATION

!

UNLIMITED PASSWORD PROTECTION

!

REAL TIME CLOCK, BATTERY BACKED

!

EXPRESSION EVALUATION

!

32 BIT / FLOATING POINT MATH

!

DIRECT, NETWORK ( One family of PLCs ) OR MODEM LINK TO

PLC CONTROL SYSTEM

!

NEMA 4/IP65

MODEL CL40 - PARADIGM  2 X 40 LCD OPERATOR INTERFACE TERMINAL

GENERAL DESCRIPTION

The Model CL40 Operator Interface Terminal combines unique capabilities

normally expected only from high-end units, at a very affordable price. The
CL40 is configured using the same powerful EDICT97 Software as all Red Lion
Paradigm Operator Interfaces. The result is savings in time to get challenging
applications up and running, and frequent savings in hardware costs due to
replacing many functions usually performed in separate expensive devices.

CL40 is robustly constructed for an industrial environment. With a metal

enclosure and a non-corroding NEMA 4/IP65 front panel.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.

SPECIFICATIONS

1. 

POWER REQUIREMENT

: 11 min. to 30 max. VDC @ 3.0 W

Power Up Current

: 3.0 A for 1 msec. max.

Must use a Class 2 or SELV rated power supply.

2. 

DISPLAY

: 2 lines of 40 characters, 0.197" (5 mm) high liquid crystal display

with bright LED backlight 

3. 

KEYPAD

: 5 screen legendable soft keys, numeric pad with raise, lower,

next, previous, enter, delete, exit, menu, alarms and mute keys, all with
Tactile feedback.

4. 

MEMORY

: 128 K (64 K user) battery backed RAM (Battery life expectancy

10 years). Optional factory fit expansion to 256 K (192 user).

PHYSICAL DIMENSIONS

: L = 9.45" (240 mm), H = 4.17" (106 mm), 

D = 2.03" (51.6 mm).

6. 

CONSTRUCTION

: Steel rear metal enclosure with NEMA 4/IP65 aluminum

front plate when correctly fitted with the gasket provided. This unit is rated for
NEMA 4/IP65 indoor use. Installation Category I, Pollution Degree 2.

7. 

MOUNTING REQUIREMENTS

: Max. panel thickness is 0.375"

(9.5 mm). For NEMA 4/IP65 sealing, a steel panel with a minimum
thickness of 0.125" (3.175 mm) is recommended

8. 

FIELD CONNECTION

: Removable screw terminal blocks.

CAUTION: Read complete instructions prior to

installation and operation of the unit.

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

CL40

LCD, 2 X 40, 5 Soft keys, 256 K memory

CL400010

Battery Replacement

LCD, 2 X 40, 5 Soft keys, 128 K memory

P895xxxZ

SFEDT

BAL3R004

CL400000

Bulletin No.  CL40-A
Drawing No.  LP0521
Released  3/03

Communications Cable

EDICT-97 Development Kit. Includes Software,
Manual and 9-pin RS232 Programming cables

Summary of Contents for CL40

Page 1: ...y command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the unit SPECIFICATIONS 1 POWER REQUIREMENT 11 min to 30 max VDC 3 0 W Power Up Current 3 0 A for 1 msec max Must use a Class 2 or SELV rated power supply 2 DISPLAY 2 lines of 40 characters 0 197 5 mm high liquid crystal display with bright ...

Page 2: ...requirements via a powerful program language For example a program designated Calculate Volume which determines the amount of fluid in a round tank at specific temperatures could be created This program would be triggered to run and display each time the page denoted as Volume Now is requested The ability to customize to your application s specialized needs is easily solved with the user program c...

Page 3: ...it board This should be clearly visible Remove the battery from its holder Place the new battery in the holder The terminal s power supply can now be disconnected if you re applied power in the step above Replace the lid screws and connector by following the above procedure in reverse You may like to make a note of the date the battery was replaced to allow planned maintenance to be carried out If...

Page 4: ...used by its negligence RLC does not warrant any of its software products to be free from error or to be fit for any particular purpose Neither is the software guaranteed to provide operation without interruption The customer s sole remedy in case of failure is the refund of the purchase price of the software The customer in applying the products and software described herein accepts that the produ...

Reviews: