82
Load Break Switch Control
ERT-200S
7.2.8.
IEC 104 Parameter Setting
Communication Config/ 6. IEC 101 Parameter
Range
Default
Step
IEC60870-5-104 protocol setting menu is as following.
Communication Config/ 6. IEC 101 Parameter / 1. T0 Off Line Poll Period
Range
1 ~255
Default
1
Step
1s
Network connection establishment timeout
Communication Config/ 6. IEC 104 Parameter / 2. T1 Ack Period
Range
1 ~ 255
Default
1
Step
1s
Response timeout
Communication Config/ 6. IEC 104 Parameter / 3. T2 SFrame Period
Range
1 ~ 255
Default
10
Step
1s
A S-format frame (ACKRSN) will be sent at the latest
after this time starting from the last received telegram
from the server.
Communication Config/ 6. IEC 104 Parameter / 4. T3 Test Period
Range
1 ~ 255
Default
20
Step
1s
An U-format frame (TESTFR) will be sent at the latest after
this time starting from the last received telegram from
the server.