47
NOTE: If an edge is activated twice or a second edge is
activated before a limit is hit (full open or close) operator will
stop and sound a warning horn. To reactivate system turn
operator power switch off then on.
NON-CONTACT SENSOR INSTALLATION
1. Install photoelectric cell as close to inside of gate as
possible.
2. Photocells should be installed across the gate
opening and behind the gate (as shown below) at
least 10 inches above ground.
NOTE:
A separate pedestrian gate must be installed if
there is no other entry access but the vehicular gate.
Photo Electric Reflector
(Mount Past Gates Full
Close Position )
Photo Electric Cell
(For Close Direction)
Photo Electric Reflector
(Mount Past Gates Full
Open Position)
Photo Electric Cell
( For Open Direction)
48
3. Connect
NON-CONTACT
sensors to the control board
as shown below.
NOTE: Close photocell is connected to “CLO PHO” and
“COM” terminals. Open photocell is connected to “OPN
PHO” and “COM” terminals.
AFTER SENSORS ARE CONNECTED:
1. Turn on power.
2. Make sure the photo-beams are properly aligned per
the manufacturer’s specifications.
3 . Test the
CLOSE
obstruction sensing system for proper
operation, by blocking the beam across the gate
opening while the gate is running closed.
NOTE: The gate should stop and reverse a short distance
and then stop.
4. Run operator to close limit.
5. Test the
OPEN
obstruction sensing system by
blocking the beam mounted at the back area of the
gate while the gate is running open.
NOTE: The operator will stop, wait approximately 5 seconds
and then continue running open.
TB2
NON CONTACT SENSOR CONNECTION
Close Photocell
Sensor
Open Photocell
Sensor
Reflector
Reflector
OP
N
CL
O
ST
O
CO
M
CO
M
CO
M
OP
N
PH
O
CL
O
PH
O
SH
W