V1.01
48
Max. charging current via solar (Adc)
80
Maximum efficiency
98%
AC-charger
Max. charging current via input (Aac)
30
60
Maximum charging current
110
140
General
Humidity Protection
5% tot 95% real humidity (non condensation)
Operating temperature
-10°C
̴
50°C
Storage temperature
-15°C
̴
60°C
Dimensions
272 355*100
298*468*125
PB.UPS.2K24
PB.UPS.3K24
PB.UPS.5K48
Low DC -Warning Voltage
At load < 20%
22,0Vdc
44,0Vdc
20% < load < 50%
21,4Vdc
42,8Vdc
At load > 50%
20,2Vdc
40,4Vdc
Low DC -Return Voltage Warning
At load < 20%
23,0Vdc
46,0Vdc
20% < load < 50%
22,4Vdc
44,8Vdc
At load > 50%
21,2Vdc
42,4Vdc
Lage DC cut-off voltage
At load < 20%
21,0Vdc
42,0Vdc
20% < load < 50%
20,4Vdc
40,8Vdc
At load > 50%
19,2Vdc
38,4Vdc
High DC recovery voltage
27Vdc
58Vdc
High DC cut-off voltage
30Vdc
60Vdc
Charging current algorithm
Lead Acid Battery
lithium battery
Summary of Contents for LfeLi-48100TB
Page 10: ...V1 01 10...
Page 11: ...V1 01 11 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48...
Page 12: ...V1 01 12...
Page 62: ...V1 01 62...
Page 63: ...V1 01 63 PB SC12 170...
Page 64: ...V1 01 64...
Page 81: ...V1 01 81 PB Li 12 100D...
Page 82: ...V1 01 82...
Page 100: ...V1 01 100...
Page 101: ...V1 01 101 LfeLi 48100TB...
Page 102: ...V1 01 102...
Page 105: ...V1 01 105 Product structure LFeLi frontpanel...
Page 137: ...V1 01 137 APPENDIX...
Page 138: ...V1 01 138...
Page 139: ...V1 01 139 COMPOSITION AND SETTINGS SYSTEMS PB UPS 2 2 24...
Page 141: ...V1 01 141 PB LSC 1 PB SC12 170 PB UPS 2K24...
Page 142: ...V1 01 142...
Page 143: ...V1 01 143 PB UPS 3 5 24...
Page 145: ...V1 01 145 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...
Page 146: ...V1 01 146 PB UPS 3K24 dimensions in mm...
Page 147: ...V1 01 147 PB UPS 5 5 48...
Page 149: ...V1 01 149 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...
Page 150: ...V1 01 150 PB UPS 5K48 dimensions in mm...
Page 151: ...V1 01 151 PB UPS 10 10 48...
Page 153: ...V1 01 153...
Page 154: ...V1 01 154 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...
Page 155: ...V1 01 155 PB UPS 5K48 dimensions in mm...
Page 156: ...V1 01 156 PB UPS 15 15 48...
Page 158: ...V1 01 158...
Page 159: ...V1 01 159 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...
Page 160: ...V1 01 160 PB UPS 5K48 dimensions in mm...
Page 161: ...V1 01 161 PB UPS 2 2 24 Li...
Page 163: ...V1 01 163 PB LSC 1 PB Li 12 100D...
Page 164: ...V1 01 164 PB UPS 2K24...
Page 165: ...V1 01 165 PB UPS 3 5 24 Li...
Page 167: ...V1 01 167 PB LSC 1 PB Li 12 100D...
Page 168: ...V1 01 168 PB UPS 2K24...
Page 169: ...V1 01 169 PB UPS 5 5 48 Li...
Page 171: ...V1 01 171 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Page 172: ...V1 01 172 PB UPS 5K48 dimensions in mm...
Page 173: ...V1 01 173 PB UPS 10 10 48 Li...
Page 175: ...V1 01 175 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Page 176: ...V1 01 176 PB UPS 5K48 dimensions in mm...
Page 177: ...V1 01 177 PB UPS 15 15 48 Li...
Page 179: ...V1 01 179 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Page 180: ...V1 01 180 PB UPS 5K48 dimensions in mm...
Page 183: ...V1 01 183 ANL MEGA...
Page 190: ...V1 01 190...
Page 191: ...V1 01 191...
Page 192: ...V1 01 192...