Gamatronic Electronic Industries Ltd.
User Guide
µ
PS-SP 3:3, 3x220 in, 3x208 60 Hz out
Safety Precautions
1
1. SAFETY PRECAUTIONS
1.1 Do’s
•
Read this manual carefully before operating the UPS.
•
Review the safety precautions described below to avoid damaging
users or equipment.
•
Install the UPS in a clean and well-ventilated location.
•
Leave at least 20 cm of clearance space between the ventilation holes
of the UPS and other objects or walls.
•
The UPS must be well grounded to the building’s grounding system
with a conductor that has a current carrying capacity that matches the
rating of the UPS.
•
If the unit contains an external battery cabinet, periodically check the
grounding connection between the external cabinet and the main UPS
cabinet
. (
The battery’s cabinet body must be connected with the
grounding screw located on the electronic cabinet or directly to the
grounding circuit
.)
•
Use the UPS only for its intended purpose.
•
Allow only qualified technicians to service the UPS. There are no user-
serviceable components.
Do not try to repair it yourself!
WARNING
Appropriate precautions should be taken during inspection and servicing; there
is a risk of lethal electric shock. The battery cabinet contains 12-Volt batteries
that provide high voltage even when the UPS is not connected to the mains.
1.2 Don’ts
•
Do not open the cover under any circumstances.
•
Do not insert any objects through the ventilation holes.
•
Do not put objects on the UPS.
•
Do not move the UPS while it is operating.
•
Do not turn the UPS upside down during transportation.
•
Do not connect or disconnect the cable to the battery cabinet before the
battery circuit breaker is turned off
•
Do not turn on the battery circuit breaker when the battery cabinet is
disconnected from the UPS.
WARNING
Do not touch the battery terminals of external batteries with bare hands
.